Product Details
| Property | Value |
|---|---|
| Product Category | Power |
| Volts | 600 |
| UL Listings | Single conductors in accordance with performance requirements of ICEA S-95-658 and UL 44 Class XL |
| Performance Standards | Cable components are in compliance with the maximum leachable lead level required by the EPA in 40CFR, Part 261 |
| Construction - Jacket | Reduced wall, black, flame retardant, low smoke, zero halogen, crosslinked polyolefin jacket |
| Construction - Insulation | Flame retardant crosslinked polyolefin meeting performance requirements of ICEA S-95-658 and UL 44 Class XL |
| Construction - Ground Wire(s) | Annealed tin-coated copper, Class “B” strand, sized to comply with UL 1277 requirements |
| Construction - Fillers | As applicable |
| Construction - Conductor | Annealed, tin-coated copper, Class “B” strand (ASTM B8 & B33) |
| Construction - Circuit Identification | Printed numbers per ICEA Method 4 |
| Construction - Binder Tape | Helically applied polyester |
| Applications | Harsh Environment Power Control Instrumentation |
| Market Served | Nuclear |
| Temperature | 90ºC |
Product Resource download links.
