Product Details
| Property | Value |
|---|---|
| Performance Standards | IEEE 1202/FT4 flame test and ICEA 70,000 BTU/hr flame test (T-30-520) • Flame test Type A as defined in ICEA S-95-658-1999 sec. 6.8.2 • Rated for CT Use 1/0 AWG and larger |
| Volts | 1000 |
| UL Listings | Type RHW-2 (UL 44) in accordance with NEC • UL VW-1 • Passes vertical flame test Type A as defined in ICEA S-95-658-1999 sec. 6.8.2 • Type ST1 (limited smoke) per UL 1277, UL 1685, and UL 2556 • sunlight resistance (Black Only) • 90ºC for both wet and dry locations• gasoline and oil resistant |
| cUL Listing | Type RW90 (CSA 22.2 No. 38) in accordance wtih CEC • Passes vertical flame test Type A as defined in ICEA S-95-658-1999 sec. 6.8.2 • Type ST1 (limited smoke) per UL 1277, UL 1685, and UL 2556 • sunlight resistance (Black Only) •90ºC for both wet and dry locations • gasoline and oil resistant |
| CSA Listings | CSA 22.2 No. 38 |
| Construction - Separator Tape | Helically applied polyester (where required) |
| Construction - Insulation | Flame retardant low Smoke Zero Halogen crosslinked polyolefin |
| Construction - Color | Black (Also available in pigmented colors or colored stripes) |
| Region | Canada |
| Product Category | Power |
| Market Served | Mining & Industrial OEM |
| Temperature | 90ºC |
| Applications | Harsh Environment Power Control Instrumentation |
| Construction - Conductor | Annealed, tin-coated copper, Class B strand per ASTM B-8 & B-33 |
Product Resource download links.