VITALink® MC 2-Hour Fire Rated Power Cable

https://smartbim-library-production.s3.amazonaws.com/manufacturers/7dd0a216-b007-4fcf-8fdd-ea9084602d12/products/aef335f9-8ddc-4412-a6c6-9495c11b3272/889fd39b-f2bc-4450-9dd0-4c7772e8651b/VITALink® MC 2-Hour Fire Rated Power Cable.png

Applications

Fire & Life Safety

Description


VITALink® MC is a 600V 2-hour fire rated cable listed to UL2196. When installed per systems FHIT 120, 120A, and 60, plus the NEC, VITALink MC meets the code requirements for 2-hour Fire Rated Circuits, Electrical Circuit Integrity Systems, Survivability, and Circuit Integrity. VITALink MC Cables offer lowered cost, reliability and ease of installation advantages over MI cable and other methods of providing fire rated circuits. The equipment grounding copper armor is terminated with commercially available brass MC connectors and the cable connections are made without the need for splicing or use of special tools. Compared to Mineral Insulated (MI) cable, VITALink MC is not exposed to costly field expenses in preparing cable ends, special panel penetrations, additional flexible terminations and the splicing of shorter lengths in longer runs. VITALink MC is not susceptible to failures caused by moisture ingress through leaky seals or faulty storage. (VC01-VITALink)

Features


- Up to 2-hour fire resistance

- Splice available

- Superior resistance to flame propagation

- Only conventional tools required to terminate

- Commercially available brass/stainless steel connectors

- Printed number coding allows for easy identification (ICEA Method 4)

- Labor savings on termination, installation, and handling

- Made in USA

- Superior impact & crush resistance

- Low smoke, low toxicity, halogen free design

- Welded armor forms an impervious barrier

- Flexible

- Long continuous lengths available

- Multiple sizes and conductor counts available

- VFD cable design available

- Copper sheath exceeds the NEC requirement for equipment grounding conductor Table 250.122

PropertyValue
Volts600
UL ListingsUL 2196 - up to 2-hour fire rated Electrical Circuit Integrity Systems FHIT 120, 120A, and 60 of the UL Fire Resistance Directory • UL 1569 – Type MC per NFPA 70 Article 330
Performance StandardsIEEE 1202/FT4 flame test; ST1 limited smoke • Copper conductors to ASTM B8
ApplicationsFire & Life Safety
Market ServedCommercial Infrastructure
Temperature90ºC