Product Details
| Property | Value |
|---|---|
| Construction - Circuit Identification | ICEA Method 4, (ICEA Methods 1, 3 or 6 also available) |
| Construction - Binder Tape | Helically applied |
| Construction - Armor (optional) | Can be supplied with either a flat or corrugated bronze tape, helically applied |
| Construction - Insulation | Proprietary heat, moisture, oil and chemical resistant, flame retardant cross-linked polyethylene (XLPE), ICEA S-95-658 Table 3-1 Column “B” thickness |
| Construction - Fillers | (Where required) |
| Construction - Conductor | Stranded, tin coated copper |
| Volts | 1000 |
| UL Listings | Jacket UL 1277 Class XL/90°C |
| Performance Standards | Conductors ASTM B-8 and B-33 • Insulation ICEA S-95-658 (formerly S-66-524) • ICEA Publication T-33-655, Type II • IEEE-383 1974 flame test (70,000 BTU/hr) and ICEA T-30-520 vertical tray flame test |
| Construction - Jacket | Moisture, heat, ozone, sunlight, oil and chemical resistant, flame retardant, Low Smoke/Zero Halogen cross-linked polyolefin (XLPO) |
| Product Category | Power, Signal |
| Applications | Harsh Environment Power Control Instrumentation |
| Market Served | Transit |
| Temperature | 90ºC |
Product Resource download links.

