VITALink® 2-Hour Fire Resistive Dual Rated CI/CIC Cable

https://smartbim-library-production.s3.amazonaws.com/manufacturers/7dd0a216-b007-4fcf-8fdd-ea9084602d12/products/e5f60b6d-55ca-4680-b770-a605fa0b25e3/3964a85c-dfcf-43ee-9045-cbae17f3c89c/VITALink® 2-Hour Fire Resistive Dual Rated CI CIC Cable.png

Applications

Fire & Life Safety

Description


Rated as both Circuit Integrity (CI) and Circuit Integrity in Conduit (CIC), VITALink® CI/CIC cables can be installed either with or without conduit, depending on the application and code requirements. As CI, also referred to as CI Free Air, VITALink® can be used in riser or horizontal (non-plenum) installations without conduit. The cable must be installed per the NEC code and meet all national and local code requirements. As CIC, VITALink® cable must be installed as the UL listed FHIT System 40A or FHIT7 System 40A and in accordance with the manufacturer’s installation instructions. These systems require use of specific hardware including conduit, couplings, pulling lubricant, pull boxes, and supports. In areas such as plenum airspace, VITALink® must be installed in conduit. (VC04)

Features


- Withstands temperatures up to 1850°F & ensures 2 hour circuit protection

- Meets survivability requirements of NFPA 72 Level 2 and 3

- Listed for use in the United States (free air and conduit) & Canada (in conduit only)

- Sunlight resistant & suitable for use in wet locations

- Solutions for both plenum and riser installations

- No special tools or training required

- No termination kits, brass fittings, or stainless steel straps needed

- Installation requirements are outlined in manufacturer’s instruction guide

- All required hardware components are commercially available off-the-shelf

PropertyValue
Construction - Cabling2 Conductors
Construction - Conductor18-12 AWG Solid Bare Copper and 16-12 AWG Stranded Bare Copper
Construction - InsulationLow Smoke, Zero Halogen Thermoset Fire-Roc®
Construction - Drain WireStranded Bare Copper (Shielded constructions only)
Construction - JacketRed Non-Halogen Flame Retardant Polyolefin (Sequential footage markers every 2 feet) Other jacket colors & non-black jacket striping available upon request
Construction - ShieldCopper/Polyester Tape (Shielded constructions only)
Construction - TapeFlame Retardant Tape
CSA ListingsFAS 105 ST1 FT4
Performance StandardsANSI/UL 2196 2 Hour fire rating for use in FHIT System 40A (See UL Fire Directory R27557) • ULC-S139/2196 Listed with Hose Stream Test for use in FHIT7 System 40A • NFPA 70, 72, 130, and 502 • Sunlight Resistant • For use in Wet Locations • NYC Electrical Advisory Board approval #54502, April 2017 • California State Fire Marshal Approved • RoHS Compliant
UL ListingsType FPLR-CI-ST1, CMR-CI-LS, and CL3R-CI-ST1 UL 1424 • UL 13 • UL 444
Volts300
Product CategoryCircuit Integrity, Power
RegionCanada
ApplicationsFire & Life Safety
Market ServedCommercial Infrastructure, Transit
Temperature105ºC